WIDNR on FaceBook  WIDNR on Twitter  WIDNR on YouTube  WIDNR on Instagram  WIDNR on LinkedIn  WIDNR Podcast  WIDNR on Pinterest

ENVIRONMENTAL CLEANUP & BROWNFIELDS REDEVELOPMENT
BRRTS on the Web

Click the Location Name or FID below to view the Location Details page. If additional Activities are present at this location, they may be accessed from Location Details.

ACTIVITY DETAILS

 
04-38-584329 JOHNSON CONTROLS INC SPILL
Activity Type / Status Jurisdiction
SPILL  CLOSED DNR RR
Location Name County DNR Region
JCI/TYCO MARINETTE NORTHEAST
Address Municipality
1 STANTON ST MARINETTE
PLSS Description Latitude (WGS84) Longitude (WGS84) Google Maps RR Sites Map
NE 1/4 of the SW 1/4 of Sec 05, T30N, R24E 45.097438 -87.6139398 Click to view on Google Maps using Lat/Long
Additional Location Description
BUILDING 18 ROOF DRAIN THAT DISCHARGES TO GROUND SOURFACE. SURFACE RUNOFF TO MENOMINEE RIVER
Additional Activity Details Acres
UNKNOWN
Facility ID PECFA No. EPA ID Start Date End Date
438039470 2019-04-25 2019-09-12
Characteristics
Above Ground
Petrol Tank

Drycleaner
EPA
NPL Site
EPA
Superfund
PECFA Funds
Eligible

PFAS

ROW Impact

Sediments
Underground
Petrol Tank
WI DOT
Site
 
Site Files
Name File
Site File Documentation for Activity Download PDF Document
Actions
Date Code Name File Comment
2019-09-12 11 Spill Activity Closed
2019-04-25 1 Spill Incident Occurred
2019-04-25 5 Notification of Hazardous Substance Spill
Spill Details
SERTS Spill ID Spill Occurred Date/Time Spill Reported Date/Time
20190425NE38-1 2019-04-25  1800 2019-04-25  1855
Description of Incident/General Comments
HOLDING TANK WITH 3% AFFF FOAM WAS OVERFILLED, DISCHARGE OF AFFF FROM VENT PIPE ON TOP OF THE TANK TO THE ROOF OF BUILDING 18, WENT DOWN ROOF DRAIN. 1-10 GALLONS OF 3% AFFF WENT TO INDUSTRIAL SEWER LINE (INDUSTRIAL LINE THAT GOES TO TURNING BASIS - CONTAINS NON-CONTACT, BOILER, AND STORM WATER). MAJOR RAIN EVENT DURING THE NIGHT OF APRIL 25, 2019. DURING THAT TIME A TANK CONTAINING 3% AFFF FOAM WAS OVERFILLED AND RELEASE THE FOAM OUT VENT PIPE ONTO ROOF OF BUILDING 18. THE SPILL (ESTIMATED BETWEEN 1 TO 10 GALLONS OF FOAM) WENT DOWN ROOF DRAIN AND INTO THE INDUSTRIAL SEWER LINE. THE INDUSTRIAL SEWER LINES IS A COMBINATION OF STORM WATER, NON-CONTACT COOLING WATER, ETC. THAT DISCHARGES TO THE MENOMONEE RIVER. THIS WATER IS NOT TREATED BEFORE DISCHARGING TO THE RIVER. THE ROOF DRAINS AND 2 STORM WATER CATCH BASINS WERE IMMEDIATELY BLOCKED OFF. CLEAN HARBORS WAS CONTACTED TO ASSESS THE SITUATION, DECONTAMINATE THE AREA, AND RECOVER LIQUIDS FROM THE STORM DRAIN LINES AND CATCH BASINS BLOCKED OFF.
Type of Location
CHEMICAL COMPANY (PRODUCTION/PROCESSING/STORAGE/REPACKAGING)
Spill Cause
OVERFILL (STORAGE TANK, VEHICLE OR EQUIPMENT) 
Description of Cause or Additional Details
TONIGHT AT 6:00PM JCI NOTICED AFFF (FIREFIGHTING FOAM) HOLDING TANK WITH 3% AFFF FOAM WAS OVERFILLED, DISCHARGE OF AFFF FROM VENT PIPE ON TOP OF THE TANK TO THE ROOF OF BUILDING 18, WENT DOWN ROOF DRAIN. 1-10 GALLONS OF 3% AFFF WENT TO INDUSTRIAL SEWER LINE (INDUSTRIAL LINE THAT GOES TO TURNING BASIS - CONTAINS NON-CONTACT, BOILER, AND STORM WATER). THE STORM WATER IN THIS LINE DOES NOT GO THROUGH ANY PRETREATMENT/TREATMENT (THE ROOF WATER) BEFORE DISCHARGING AT WPDES OUTFALL 001.
Description of Environmental Impact
POTENTIAL TO STORM SEWER.
Cleanup Efforts at Time Incident Reported
STOPPING FROM GOING TO ROOF, PLUGGING DRAINS, AND CONTAINERIZING ONTO TOTES FOR LATER DISPOSAL. CLEAN HARBORS WAS CONTACTED AND COMPLETED DECONTAMINATION OF THE AREAS AFFECTED WITH A THOROUGH AREA WASH-DOWN OF THE ASPHALT AREAS AND COLLECTION AND REMOVAL OF THE WASH-DOWN WATER AND PUDDLED WATER. APPROXIMATELY 5,000 GALLONS OF CLEAN WATER WHICH WAS COLLECTED VIA VACUUM TRUCK AND THEN STAGED IN A 20,000 GALLON FRAC TANK ONā€SITE. THIS MATERIAL WAS MIXED WITH OTHER IMPACTED WATER WHICH WAS SENT FOR DEEPWELL INJECTION EITHER AT VICKERY, OH OR DEER PARK, TX.
Spiller Actions
Action Comment
Flow Stopped
Storm Sewer Blocked Off
Vacuum
Contractor Hired CLEAN HARBORS
Waste Destination DEEPWELL INJECTION
Substances
Substance Type Amt Released Units
Other Substance Not Listed (AFFF FIRE FIGHTING FOAM 3%) Other 10 Gal
Waste Destination
Destination Comment
OTHER: DEEPWELL INJECTION
Responsible Party
JOHNSON CONTROLS INC 1 STANTON ST, MARINETTE, WI 54143
For More Information on this Activity
Northeast Region Contact: Denise Danelski  denise.danelski@wisconsin.gov
584329 | 04-38-584329
BOTW Release 4.9 | 04/23/2024 | Release Notes  Help  Disclaimers  Glossary of Terms  Supplemental Pages